Power supply: 230 VAC +10 % -15 % 50/60 Hz
115 VAC +10 % -15 % 50/60 Hz (optional)
Ambient temperature
Operation:
+0 °C … +60 °C
Ambient temperature
Transport and storage:
-25 °C … +60 °C
Resolution per analogue input: 999 digit, 10 bit
Three-point step Recommended run time of the servomotor: 30 s … 60 s
Continuous output: Apparent ohmic resistance: 0 … 10 V > 5 kΩ
0/4 … 20 mA < 600 Ω
Digital signal input: 16 via floating contact
24 VDC or optional via 230 V module type 660R0018
Number of curve set: 2 per channel (e.g. for oil/gas dual-fuel burner) optional 4 or 8
BUS connection:

Via 25-pole Sub-D socket

BUS card for the following systems:

  • INTERBUS-S (Phoenix)
  • PROFIBUS
  • Modbus
  • Ethernet (Modbus TCP)