| Power supply: | From 115 VAC -15 % To 230 VAC +10 % 50/60 Hz |
| Ambient temperature operation: |
+0 °C … +60 °C |
| Ambient temperature Transport and storage: |
-25 °C … +60 °C |
| Resolution, per analogue input: |
999 digit, 10 bit |
| Recommended running-time for actuators: | 30 s … 60 s |
| Continuous outputs: | 0…10 V > 5 kΩ |
| Load: | 0/4 … 20 mA < 600 Ω |
| Digital signal input: |
14 (The line shall not be longer than 10 m) |
| Digital outputs: | Main gas 1, main gas 2, oil valves, ignition valves, ignition transformer, fan, oil pump, fault |
| Number of curve sets: | 2 per channel (e.g. for oil/gas multi-burner) |
| BUS connection: |
Via LSB-adapter BUS-connection optional for: |